Prosoft-technology 3170-MBS Manual de usuario Pagina 37

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 55
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 36
3170-MBS ♦ Flex Platform Example Address Mapping
Modbus Slave Interface Module User Manual
ProSoft Technology, Inc. Page 37 of 55
October 27, 2010
7.3 Function Code Address Ranges
Function Address
Type
Horizontal
Read
Modbus
Address
Horizontal
Write
Modbus
Address
Vertical
Read
Modbus
Address
Vertical
Write
Modbus
Address
1 Bit 0 to 1919 40001 to
40120
N/A N/A N/A N/A N/A N/A
Bit 3200 to 5119
40200 to
40320
N/A N/A N/A N/A N/A N/A
2 Bit 0 to 1919 40001 to
40120
N/A N/A N/A N/A N/A N/A
Bit 3200 to 5119
40200 to
40320
N/A N/A N/A N/A N/A N/A
3 Register 0 to 119 40001 to
40120
N/A N/A 1000 to
1119
41001 to
41120
N/A N/A
Register 200 to 319 40200 to
40320
N/A N/A 1200 to
1319
41201 to
41320
N/A N/A
4 Register 0 to 119 40001 to
40120
N/A N/A 1000 to
1119
41001 to
41120
N/A N/A
Register 200 to 319 40200 to
40320
N/A N/A 1200 to
1319
41201 to
41320
N/A N/A
5 Bit N/A N/A 3200 to 5119
40201 to
40320
N/A N/A N/A N/A
6 Register N/A N/A 200 to 319 40201 to
40320
N/A N/A 1200 to
1319
41201 to
41320
16 Register N/A N/A 200 to 319 40201 to
40320
N/A N/A 1200 to
1319
41201 to
41320
Vista de pagina 36