MVI56-101S ControlLogix Platform Configuring the MVI56-101S Module
IEC 60870-5-101 Slave Communication Module User Manual
ProSoft Technology, Inc. Page 61 of 193
August 2, 2011
2.12 [M_IT_NA_1]
This section defines the monitored integrated totals (counter) database. This
information is sourced from the database and is transferred to the remote Master
unit. This section takes the following parameters:
P
OINT #
DB
ADDRESS
G
ROUPS
IV
DB BIT
Each point consumes four 8-bit bytes (two 16-bit words). The DB ADDRESS value
corresponds to the double-word offset address in the database.
The DB
ADDRESS should be located in a database area that is being constantly
moved from the module to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.