Reference MVI56E-MNETCR ♦ ControlLogix Platform
User Manual Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis
Page 144 of 159 ProSoft Technology, Inc.
June 14, 2011
2 Edit the Module Properties. Select the R
EQUESTED
P
ACKET
I
NTERVAL
value
for scanning the I/O on the module. This value represents the minimum
frequency that the module will handle scheduled events. This value should
not be set to less than 1 millisecond. The default value is 5 milliseconds.
Values between 1 and 10 milliseconds should work with most applications.
3 Save the module. Click OK
to dismiss the dialog box. The C
ONTROLLER
O
RGANIZATION
window now displays the module's presence.
4 Copy the Controller Tags from the sample program.
5 Copy the User Defined Data Types from the sample program.
6 Copy the Ladder Rungs from the sample program.
7 Save and Download (page 43) the new application to the controller and place
the processor in run mode.