PLX8x-MNET-61850 Communication Gateway Example Configurations
Modbus TCP/IP to IEC 61850 User Manual
ProSoft Technology, Inc. Page 81 of 228
May 14, 2014
b DATA-SET. To configure the ProSoft gateway to subscribe to the IED’s
GOOSE message, drag and drop the yellow folder showing the GOOSE
name to the right side of the window.
When you drag and drop the GOOSE DATA-SET, the right-hand side of the
window will automatically populate with one row for each Data Attribute in
that DATA-SET.
c Choose MAPPING / SAVE.
d On the Quantum, Premium, or M340 icon, choose PLC Map View, and
left-click the EXPORT PROCESSOR FILES button.
e Go into Unity Pro and import the files.
f SAVE the Project