Prosoft-technology PS69-DPS Manual de usuario Pagina 93

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 108
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 92
PS69-DPS CompactLogix or MicroLogix Platform Reference
Profibus DP Slave Communication Module User Manual
ProSoft Technology, Inc. Page 93 of 108
May 9, 2014
DPS_DPV1C1_ALARM_REQUEST
Parameter
Data Type
Value
Description
Reserved1
INT
0
Reserved
Reserved2
INT
0
Reserved
Reserved3
INT
0
Reserved
Command
SINT
18
Command for Service
DPV1 Class 1 Alarm Request
Reserved4
SINT
0
Reserved
Reserved5
INT
0
Reserved
SlotNumber
INT
0...254
Alarm Slot Number
SequenceNumber
SINT
0...31
Alarm Sequence Number
DataCnt
SINT
0...28
(x)
Number of User Specific Alarm Data
AlarmType
SINT
1-6,
32-126
Alarm Type:Diag,-Process,-Pull,-Plug,-Status,-Update,
Manufacturer specific
Specifier
SINT
0...7
Alarm Specifier
Bit 0...1: Alarm Specifier
Bit 2: Add Ack bit
Data[0..x]
SINT[28]
0…255
User Specific Alarm Data.
DPS_B_ACYC_C1_ALARM _CONFIRM
Parameter
Data Type
Value
Meaning
Reserved1
INT
0
Reserved
Reserved2
INT
0
Reserved
Answer
SINT
18
Answer DPS_B_ACYC_C1_ALARM
Failure
SINT
e
Error, status (see following section)
Reserved3
INT
0
Reserved
Reserved4
INT
0
Reserved
SlotNumber
INT
0...254
Alarm Slot Number, Reply from request
SequenceNumber
SINT
0...31
Alarm Sequence Number, Reply from request
DataCnt
SINT
0
not used
DataType
SINT
1-6,
32-126
Alarm Type, Reply from request
Specifier
SINT
0..7
Alarm Specifier, Reply from request
Vista de pagina 92
1 2 ... 88 89 90 91 92 93 94 95 96 97 98 ... 107 108

Comentarios a estos manuales

Sin comentarios