Page 16 AN-X2-GENI (AN-X-GENI/B) May 2013
Genius Network Configuration
Before you can scan a Genius I/O network, you must set the AN-X module’s serial bus
address and baud rate and configure the network in the AN-X2-GENI.
Set the baud rate and serial bus address before connecting to the Genius network.
Setting the Bus Address and Baud Rate
From the AN-X web interface, select Automation Network/Genius Baud/Node Settings.
Check the desired baud rate from the four supported baud rates: 38.4Kbps, 76.8 Kbps,
153.6 KBPS standard or 153.6 Kbps extended.
Enter the serial bus address (SBA) for the AN-X, in the range 0 to 31.
Click the Submit Changes button to set the Genius bus properties of the AN-X2-GENI.
Configuring the Genius Network
There are two methods of configuring the Genius I/O that the AN-X2-GENI is to scan:
autoconfiguration. The AN-X2-GENI reads the network contents by sending
messages to the attached network.