Start Here MVI56E-GSC CompactLogix or MicroLogix Platform
User Manual Enhanced Generic ASCII Serial Communication Module
Page 42 of 140 ProSoft Technology, Inc.
May 9, 2014
2 Select 1756-MODULE
3 Set the Module Properties values as follows:
Parameter
Value
Name
Enter a module identification string. Example: GSC_2.
Description
Enter a description for the module. Example: ProSoft
Enhanced Generic ASCII Serial Communication Module.
Comm Format
Select DATA-SINT.
Slot
Enter the slot number in the rack where the MVI56E-GSC
module is located.
Input Assembly Instance
1
Input Size
500
Output Assembly Instance
2
Output Size
496
Configuration Assembly Instance
4
Configuration Size
0
4 Click OK to confirm. The new module is now visible:
5 Expand the TASKS folder, and then expand the MAINTASK folder.
6 On the MAINPROGRAM folder, click the right mouse button to open a shortcut
menu. On the shortcut menu, choose NEW ROUTINE. As an alternative to
creating a separate New Routine, you could skip to Step 8 and import the
AOI for the second module into the same routine you created for the first
module.