MVI56E-MCMR ControlLogix Platform Reference
Modbus Communication Module with Reduced Data Block User Manual
ProSoft Technology, Inc. Page 183 of 225
May 13, 2014
6.6.4 Read Holding Registers (Function Code 03)
Query
Read Holding Registers (03) allows the user to obtain the binary contents of
holding registers 4xxxx in the addressed Slave. The registers can store the
numerical values of associated timers and counters which can be driven to
external devices. The addressing allows up to 125 registers to obtained at each
request; however, the specific Slave device may have restriction that lower this
maximum quantity. The registers are numbered form zero (40001 = zero, 40002
= one, and so on). The broadcast mode is not allowed.
The example below reads registers 40108 through 40110 from Slave 584
number 11.
Adr
Func
Data Start Reg Hi
Data Start Reg Lo
Data #of Regs Hi
Data #of Regs Lo
Error Check Field
11
03
00
6B
00
03
CRC
Response
The addressed Slave responds with its address and the function code, followed
by the information field. The information field contains 1 byte describing the
quantity of data bytes to be returned. The contents of the registers requested
(DATA) are two bytes each, with the binary content right justified within each pair
of characters. The first byte includes the high order bits and the second, the low
order bits.
Because the Slave interface device is normally serviced at the end of the
controller's scan, the data will reflect the register content at the end of the scan.
Some Slaves will limit the quantity of register content provided each scan; thus
for large register quantities, multiple transmissions will be made using register
content from sequential scans.
In the example below, the registers 40108 to 40110 have the decimal contents
555, 0, and 100 respectively.
Adr
Func
ByteCnt
Hi Data
Lo Data
Hi Data
Lo Data
Hi Data
Lo Data
Error Check Field
11
03
06
02
2B
00
00
00
64
CRC