MVI-ADM 'C' Programmable Preparing the MVI-ADM Module
'C' Programmable Application Development Module Developer's Guide
ProSoft Technology, Inc. Page 21 of 342
February 20, 2013
RS-232: Null Modem Connection (No Hardware Handshaking)
This type of connection can be used to connect the module to a computer or field
device communication port.
Note: For most null modem connections where hardware handshaking is not required, the Use
CTS Line parameter should be set to N and no jumper will be required between Pins 7 (RTS) and 8
(CTS) on the connector. If the port is configured with the Use CTS Line set to Y, then a jumper is
required between the RTS and the CTS lines on the port connection.