Reference MVI69-EGD ♦ CompactLogix or MicroLogix Platform
GE Ethernet Global Data Communication Module
ProSoft Technology, Inc. Page 67 of 96
November 3, 2008
Packet
Info
Description Data
Reserved:
12 4 0x HH HH HH HH
Maximum Exchanges:
16 4 0x HH HH HH HH
Capabilities Bit Mask:
20 4 0x HH HH HH HH
Reserved:
24 2 0x HH HH
Configuration Type:
26 2 0x HH HH
Identification String
(up to 80 characters):
28 XX 0x HH . . . HH
Summary PDUs
PDU Type = 7
Summary Request
The summary request PDU command permits an application program to request
a summary of the exchanges configured on a given node. This allows a user to
get a complete list of all exchanges defined. The Index field is normally 0 and is
used to request a block of summaries in nodes which contain a large number of
exchanges. A summary request sent from a requesting node must be followed by
a summary response message from the responding node.
Packet
Info
Description Data
Source Port:
7937 (0x 1F01)
Destination Port:
7937 (0x 1F01)
Length:
xx bytes (0x 00 XX)
Checksum:
xxxxx (0x XX XX)
EGD's PDU Field: Offset Bytes Hex code
PDU Type:
0 1 0x 07
Message Flag:
1 1 0x HH
Request ID:
2 2 0x HH HH
PVN1:
4 1 0x 01
Reserved:
5 1 0x HH
Message Length:
6 2 0x HH HH
Index:
8 1 0x HH
UDP
EGD:
Reserved:
9 3 0x 00 00 00