Reference ProLinx-HART ♦ ProLinx Gateway
Driver Manual HART Master with Analog I/O
Page 44 of 104 ProSoft Technology, Inc.
October 13, 2011
COMMAND 02 - Read Current And Percent Of Range
Description
This command gets the current of the loop that is forced by the HART device and the
Percent of Range of the Current.
Write Parameters
NONE
Floating Point Data Returned
Word High Byte Low Byte
0 Current (mA)
1
2 Percent of Range
3
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
Vista de pagina 43