5.1.2 Hardware Specifications
Specification Description
Dimensions Standard 1769 Single-slot module
Current Load 800 mA max@ 5 VDC
Power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus)
Operating Temp. 0 to 60°C (32 to 140°F)
Storage Temp. -40 to 85°C (-40 to 185°F)
Relative Humidity 5% to 95% (non-condensing)
LED Indicators Battery and Module Status
Application Status
Serial Port Activity
CFG Port Activity
CFG Port (CFG) RJ45 (DB-9F with supplied cable)
RS-232 only
No hardware handshaking
App Ports (P1,P2) (Serial modules) RS-232 or RS-422 (jumper selectable)
RJ45 (DB-9F with supplied cable)
RS-232 handshaking configurable
500V Optical isolation from backplane
Shipped with Unit RJ45 to DB-9M cables for each port
6-foot RS-232 configuration Cable
5.1.3 Functional Specifications
Single-slot, CompactLogix I/O compatible
Multiple modules can be placed in a rack up to the chassis power supply limit
While in 3964R with RK512 mode on PRT1 and PRT2, DB-SEND and DB-
FETCH instructions can be initiated from the CompactLogix processor or
received by the communications partner
While in 3964R without RK512 mode on PRT1 and PRT2, data can be sent
from the CompactLogix processor or be received from the communications
partner
The maximum transfer size is 512 bytes in any mode
Data byte swapping can be configured to adjust to a different word format
While in 3964R with RK512 mode on PRT1 and PRT2, evaluation of the
header information DB (data block), DW (data word) and coordination bytes 9
and 10 is possible
Communication activity and diagnostics are available through LEDs and
acknowledgment telegrams