Configuring the Processor with Concept PTQ-LNG Quantum / Unity Platform
Landis & Gyr Telegyr Interface Module
ProSoft Technology, Inc. Page 23 of 103
May 29, 2007
11 In the PLC Configuration window, open the Online menu, and then choose
Animate. This action opens the RDE Template dialog box, with animated
values in the Value field.
12 Verify that values shown are cycling, starting from address 400008 on up.
13 In the PLC Configuration window, open the Templates menu, and then
choose Save Template As. Name the template ptqclock, and then click OK to
save the template.
14 In the PLC Configuration window, open the Online menu, and then choose
Disconnect. At the disconnect message, click Yes to confirm your choice.
At this point, you have successfully
Created and downloaded a Quantum project to the PLC
Preset values in data registers that will later be monitored in the ProTalk
module.
You are now ready to complete the installation and setup of the ProTalk module.