Installing and Configuring the Module MVI46-DFCM ♦ SLC Platform
DF1 Communication Module
ProSoft Technology, Inc. Page 23 of 103
October 20, 2008
2.2.2 Port 1 Setup
Database in SLC Database in MVI46-DFCM
File M0 Offset File Register Content Description
N10:6 7 N32:10 5010 Enable
This parameter defines if this port
will be utilized. If the parameter is
set to 0, the port is disabled. A
value of 1 will enable the port.
N10:7 8 N32:11 5011 Type
This parameter defines if the port
will emulate a master or slave
device. Enter 0 to emulate a
master device and 1 to emulate a
slave device.
N10:8 9 N32:12 5012
Local Station
ID
This parameter specifies the local
station ID for all DF1 messages
sent from this master port. A
value of 255 is not permitted as
this is the broadcast address.
Valid value in the range of 0 to
254.
N10:9 10 N32:13 5013 Protocol 0=full duplex, 1=half-duplex
N10:10 11 N32:14 5014
Termination
Type
This parameter specifies the error
checking for all DF1 messages.
0=BCC, 1=CRC
N10:11 12 N32:15 5015 Baud Rate
This is the baud rate to be used
on the port. Enter the baud rate
as a value
Baud
Rate
Parameter Value
110 110
150 150
300 300
600 600
1200 12 or 1200
2400 24 or 2400
4800 48 or 4800
9600 96 or 9600
14,400 14, 114 or 14400
19,200 19, 192 or 19200
28,800 28, 288 or 28800
38,400 38, 384 or 38400
57,600 57 or 576
115,200 115 or 1152
N10:12 13 N32:16 5016 Parity
This is the Parity code to be used
for the port. The coded values are
as follows: 0=None, 1=Odd,
2=Even, 3=Mark and 4=Space.
N10:13 14 N32:17 5017 Data Bits
This parameter sets the number
of data bits for each word used by
the protocol. Valid value in the
range of 5 to 8.