Prosoft-technology MVI56E-LDM Manual de usuario Pagina 219

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 264
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 218
ControlLogix Platform "C" Programmable Cable Connections
Linux Application Development Module Developer's Manual
ProSoft Technology, Inc. Page 213 of 264
March 12, 2014
Note: Terminating resistors are generally not required on the RS-485 network, unless you are
experiencing communication problems that can be attributed to signal echoes or reflections. In
these cases, installing a 120-ohm terminating resistor between pins 1 and 8 on the module
connector end of the RS-485 line may improve communication quality.
6.4.1 RS-485 and RS-422 Tip
If communication in the RS-422 or RS-485 mode does not work at first, despite
all attempts, try switching termination polarities. Some manufacturers interpret +
and -, or A and B, polarities differently.
6.5 DB9 to RJ45 Adaptor (Cable 14)
Vista de pagina 218
1 2 ... 214 215 216 217 218 219 220 221 222 223 224 ... 263 264

Comentarios a estos manuales

Sin comentarios