Prosoft-technology MVI69E-MBTCP Manual de usuario Pagina 134

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 150
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 133
Reference MVI69E-MBTCP CompactLogix Platform
User Manual Modbus TCP/IP Enhanced Communication Module
Page 134 of 150 ProSoft Technology, Inc.
May 20, 2015
Block 8000: Response from Module to Processor
Offset
Description
0
Block ID 8000 for event command with data request
1
The next read request block identification code
2
Error Code for request:
0 = No error
-1 = Client is not enabled
-3 = Client is not active
-4 = Client busy with previous event command
-5 = Invalid Modbus command
-6 = Invalid point count for command
3 to (n-1)
Spare
7.4.8 Get Event with Data Status Block (8100)
This block requests status data for Event with Data Commands.
Block 8100: Request from Processor to Module
Offset
Description
0
Block ID 8100 status data request for Event with Data Commands.
1 to (n-1)
Spare
Where n = 60, 120, or 240 depending on the Block Transfer Size parameter.
Block 8100: Response from Module to Processor
Offset
Description
0
Block ID 8100 status data for Event with Data Commands
1
The next read request block identification code
2
Number of client records contained in block (0-19)
3
Client Index (0-19)
4
Error code for last command executed for client
5
Client Index (0-19)
6
Error code for last command executed for client
7 to 42
Data for other clients being reported
43 to (n-1)
Spare