PTQ-104S ♦ Quantum/Unity Platform Reference
IEC-60870-5-104 Server Communication Module User Manual
Page 110 of 181 ProSoft Technology, Inc.
October 5, 2009
8.1.2 General Specifications
Single Slot - Quantum backplane compatible
The module is recognized as an Options module and has access to PLC
memory for data transfer
Configuration data is stored in non-volatile memory in the ProTalk
®
module
Up to six modules can be placed in a rack
Local rack - The module must be placed in the same rack as processor
Compatible with common Quantum / Unity programming tools
Quantum data types supported: 0x, 1x, 3x, 4x
High speed data transfer across backplane provides quick data update times
Does not currently support Hot-Standby processors or applications
8.1.3 Hardware Specifications
Specification Value
Backplane Current Load 800 mA @ 5 V
Operating Temperature 0 to 60°C (32 to 140°F)
Storage Temperature -40 to 85°C (-40 to 185°F)
Relative Humidity 5% to 95% (non-condensing)
Vibration Sine vibration 4-100 Hz in each of the 3 orthogonal axes
Shock 30G, 11 mSec. in each of the 3 orthogonal axes
LED Indicators Module Status
Backplane Transfer Status
Serial Port Activity LED
Serial Activity and Error LED Status
Configuration Serial Port
(PRT1)
DB-9M PC Compatible
RS-232 only
No hardware handshaking
Application Ethernet port RJ45 Connector
Link and Activity LED indicators
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s, applied as
specified in section 5.3.2 of IEC 60950: 1991
Ethernet Broadcast Storm Resiliency = less than or equal to 5000
[ARP] frames-per-second and less than or equal to 5 minutes
duration
8.1.4 Functional Specifications
The PTQ-104S module accepts data read/write commands from a master/client
on the network. In addition, the module can be configured to generate unsolicited
messages in either a spontaneous or cyclic fashion.
The module has 4000 words of user defined internal register space that are
accessible to the protocol driver and to the Quantum processor memory. Any of
the supported database types can be individually located (within the total
database size limit of 4000 words) and each database point is mapped within the
module and can be assigned to one or more Groups.