Reference HART ProLinx Gateway
Driver Manual HART Master
ProSoft Technology, Inc. Page 59 of 119
July 7, 2009
COMMAND 15 - Read Output Information
Description
This command gets information about the Primary Variable Output Information.
Write Parameters
NONE
Floating Point Data Returned
Word High Byte Low Byte
0
1
Upper Range Value
2
3
Lower Range Value
4
5
Damping Value (Sec)
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Alarm Select Code Transfer Function Code
2 Primary Variable Range Units Code Write-Protect Code
2 Private-Label Distributor Code 0
Vista de pagina 58