ProSoft Technology ProLinx-HART Especificaciones Pagina 64

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 119
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 63
HART ProLinx Gateway Reference
HART Master Driver Manual
Page 64 of 119 ProSoft Technology, Inc.
July 7, 2009
5.2 HART Common Practice Commands
COMMAND 33 - Read Transmitter Variables
Description
This command gets four user selected dynamic Variables.
Write Parameters
Word High Byte Low Byte
0 Transmitter Variable Code For Slot 0 Transmitter Variable Code For Slot 1
1 Transmitter Variable Code For Slot 2 Transmitter Variable Code For Slot 3
Floating Point Data Returned
Word High Byte Low Byte
0
1
Variable for Slot 0
2
3
Variable for Slot 0
4
5
Variable for Slot 2
6
7
Variable for Slot 3
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Transmitter Variable Code For Slot 0 Units Code for Slot 0 Variable
2 Transmitter Variable Code For Slot 1 Units Code for Slot 1 Variable
3 Transmitter Variable Code For Slot 2 Units Code for Slot 2 Variable
4 Transmitter Variable Code For Slot 3 Units Code for Slot 3 Variable
Vista de pagina 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 118 119

Comentarios a estos manuales

Sin comentarios