ProSoft Technology ProLinx-HART Especificaciones Pagina 66

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 119
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 65
HART ProLinx Gateway Reference
HART Master Driver Manual
Page 66 of 119 ProSoft Technology, Inc.
July 7, 2009
COMMAND 35 - Write Range Values
Description
This command writes the Upper and Lower range of the Primary Variable
Write Parameters
Word High Byte Low Byte
0 Range Units Code Floating Point Upper Range Value (Byte 0)
1 Floating Point Upper Range Value (Byte 1) Floating Point Upper Range Value (Byte 2)
2 Floating Point Upper Range Value (Byte 3) Floating Point Lower Range Value (Byte 0)
3 Floating Point Lower Range Value (Byte 1) Floating Point Lower Range Value (Byte 2)
4 Floating Point Lower Range Value (Byte 3) Floating Point Lower Range Value (Byte 3)
Floating Point Data Returned
Word High Byte Low Byte
0
1
Upper Range Value
2
3
Lower Range Value
Integer Data Returned
Word High Byte Low Byte
0 STATUS WORD
1 Range Units Code 0
Vista de pagina 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71 ... 118 119

Comentarios a estos manuales

Sin comentarios