Client Error/Status Data BACnet ♦ ProLinx Gateway
Protocol Manual BACnet/IP Client Edition 2
Page 40 of 52 ProSoft Technology, Inc.
November 24, 2010
Command List Parsing
Error Word
MSB LSB Group Description
0xFF 0x01 Command
Param
Error while reading in a command. Not enough parameters are
present in the current command record to construct a command.
0xFF 0x02 Command
Param
Invalid type code entered for the enable field. Only values of 0 to
2 are accepted.
0xFF 0x03 Command
Param
Count value in command set to zero. This parameter must be set
to a value greater than or equal to 1 and less than 25.
0xFF 0x04 Command
Param
Invalid swap code entered for command. Values of 0 to 3 are only
those accepted by the program.
0xFF 0x05 Command
Param
Invalid function code entered. This parameter must have one of
the following values: 12, 14, 15 or 16.
0xFF 0x06 Command
Param
Invalid datatype selected for the command. This parameter must
be set to one of the following values: 0=analog input, 1=analog
output, 3=binary input or 4=binary output.
0xFF 0x07 Command
Param
Invalid property value for the command. Refer to the property list
for all available properties supported by the program. This does
not imply that all servers will contain this property for every object
type.