
PDPS ♦ ProLinx Gateway Diagnostics and Troubleshooting
PROFIBUS DP Slave
Page 36 of 61 ProSoft Technology, Inc.
December 31, 2008
Byte(s) Description (HEX)
12 Value of Status Register [1] (see Section 2)
13 Module State (see Section 2)
Bytes 7 through 10 Data - Specific Product Code Value
Each ProLinx application has its own, unique product code. You can determine
the product code from the Version screen in the Configuration/Debug menu.
The following table lists the product codes for some ProLinx modules that
support the PDPS protocol.
Example Product Example Product Code
5105-ASCII-PDPS ASPS
5105-DFCM-PDPS DFPS
5105-DH485-PDPS D4PS
5105-DNPM-PDPS DMPS
5105-DNPS-PDPS D3PS
5105-I101S-PDPS ISPS
5105-I103M-PDPS PSI3
5105-MCM-PDPS PDSM
Sample Diagnostics reported to master.
Translated as follows:
Extended diagnostics length 0E= 14 bytes, Product Version 56 = "V", 30 =
"0", 31 = "1", 2E = ".", 30 = "0", 35 = "5", Product Name 50 = ""P", 44 = ""D", 53
= "S", 34 = "4" (MVI46),
Status Register [0] 41 = SPC3 in passive idle and WD-State is in DP_Control
State, Status Register [1] 03 = 1.5 Baud rate, Module State 04 = not in data
exchange
Comentarios a estos manuales