MVI69-GSC ♦ CompactLogix or MicroLogix Platform Ladder Logic
Generic ASCII Serial Communication Module User Manual
ProSoft Technology, Inc. Page 49 of 102
September 24, 2010
This action opens the following dialog box:
2 Select the 1769-Module (Generic 1769 Module) from the list and click OK.
3 Enter the Name, Description and Slot options for your application, using the
values in the illustration above. You must select the Comm Format as Data -
INT in the dialog box, otherwise the module will not communicate over the
backplane of the CompactLogix rack.