MVI56-DFCMR ControlLogix Platform Installing and Configuring the Module
DF1 Interface Module with Reduced Data Block
Page 28 of 113 ProSoft Technology, Inc.
October 20, 2008
Register Content Description
5015 Baud Rate
This is the baud rate to be used on the port. Enter the
baud rate as a value.
Baud Rate Parameter Value
110 110
150 150
300 300
600 600
1200 12 or 1200
2400 24 or 2400
4800 48 or 4800
9600 96 or 9600
14,400 14, 114 or 14400
19,200 19, 192 or 19200
28,800 28, 288 or 28800
38,400 38, 384 or 38400
57,600 57 or 576
115,200 115 or 1152
5016 Parity
This is the Parity code to be used for the port. The
coded values are as follows: 0=None, 1=Odd,
2=Even.
5017 Data Bits
This parameter sets the number of data bits for each
word used by the protocol. Enter a value in the range
of 5 to 8.
5018 Stop Bits
This parameter sets the number of stop bits to be
used with each data value sent. Enter a value of 1 or
2.
5019
Minimum Response
Delay
This parameter sets the number of milliseconds to
wait before a response message is sent out of the
port. This parameter is required when interfacing to a
slow responding device. Enter a value in the range of
0 to 65535.
5020 RTS On Delay
This parameter sets the number of milliseconds to
delay after RTS is asserted before the data will be
transmitted. Enter a value in the range of 0 to 65535.
5021 RTS Off Delay
This parameter sets the number of milliseconds to
delay after the last byte of data is sent before the
RTS modem signal will be set low. Enter a value in
the range of 0 to 65535.
5022 Use CTS Line
This parameter specifies if the CTS modem control
line is to be used. If the parameter is set to 0, the
CTS line will not be monitored. If the parameter is set
to 1, the CTS line will be monitored and must be high
before the module will send data. Normally, this
parameter is required when half-duplex modems are
used for communication (2-wire).