MVI56E-SIE ♦ ControlLogix Platform Diagnostics and Troubleshooting
Client Communication Module User Manual
ProSoft Technology, Inc. Page 129 of 168
September 6, 2012
4.3.2 Configuration Error Word
The Configuration Error Word contains Client configuration error indications, in a
bit-mapped format. Specific bits in the module's Configuration Error Word are
turned on (set to 1) to indicate various configuration errors. The Configuration
Error Word appears in the SIE.STATUS.ClientStatus[x] controller tag array.
Bits set to 1 in the Configuration Error Word indicate the following errors.
Reserved - not currently used
Reserved - not currently used
Reserved - not currently used
Reserved - not currently used
Invalid retry count parameter
The float flag parameter is not valid.
The float start parameter is not valid.
The float offset parameter is not valid.
The ARP Timeout is not in range (ARP Timeout parameter 0 or
greater than 60000 milliseconds) and will default to 5000
milliseconds.
The Command Error Delay is > 300 and will default to 300.
Reserved - not currently used
Reserved - not currently used
Reserved - not currently used
Reserved - not currently used
Reserved - not currently used
Reserved - not currently used
Combinations of errors will result in more than one bit being set in the error word.
Correct any invalid data in the configuration for proper module operation. A value
of zero (0) in this word indicates all bits are clear, which means that all module
configuration parameters contain valid values. However, this does not mean that
the configuration is valid for the user application. Make sure each parameter is
set correctly for the intended application.