MVI56E-SIE ControlLogix Platform Start Here
Client Communication Module User Manual
ProSoft Technology, Inc. Page 25 of 168
September 6, 2012
Adding Multiple Modules (Optional)
Important: If the application requires more than one MVI56-SIE module in the
same project, follow the steps below.
1 In the I/O CONFIGURATION folder, click the right mouse button to open a
shortcut menu, and then choose NEW MODULE.
2 Select 1756-MODULE.
3 Fill the module properties as follows:
Parameter
Value
Name
Enter a module identification string. Example: SIE_2.
Description
Enter a description for the module. Example: SIEMENS
INDUSTRIAL ETHERNET CLIENT COMMUNICATION MODULE
Comm Format
Select DATA-INT.
Slot
Enter the slot number in the rack where the MVI56E-SIE
module is located.
Input Assembly Instance
1
Input Size
250
Output Assembly Instance
2
Output Size
248
Configuration Assembly Instance
4
Configuration Size
0