Configuring the MVI56E-SIE Module MVI56E-SIE ControlLogix Platform
User Manual Client Communication Module
Page 80 of 168 ProSoft Technology, Inc.
September 6, 2012
7 Select each parameter and edit its value as shown below, except for the IP
address. Use the IP address of the S7-300 processor that the command is
addressing. Click the OK button when all the configuration parameters have
been entered.
Note: In this example, the Internal Address parameter configures this command to place the data
received from S7-300 processor into the first register of the module’s Read Data area. The start
address of the module’s Read Data area is determined by the Read Register Start parameter in the
module configuration. By default, the Read Register Start parameter is set to 0.