It would imply that the parameter points would be configured as follows:
M_ME_NA
Monitored Measured Normalized Point
Associated Parameter Point
In order to send a change of deadband for M_ME_NA Point 400, the Client would
send a command type 110 to point 2400.
M_ME_NB
Monitored Measured Normalized Point
Associated Parameter Point
In order to send a change of deadband for M_ME_NB Point 500, the Client would
send a command type 110 to point 2500.