Reference DFNT ProLinx Gateway
Protocol Manual EtherNet/IP Explicit Messaging Client/Server
Page 114 of 124 ProSoft Technology, Inc.
July 24, 2013
5.11 SLC 5/05 Processor
The module can be used to receive messages from a SLC 5/05 containing an
Ethernet interface. The module supports both read and write commands. A
discussion of each operation is provided in the following topics.
5.11.1 SLC5/05 Write Commands
Write commands transfer data from the SLC processor to the DFNT module. An
example rung used to execute a write command is shown in the following
diagram:
Set the READ/WRITE parameter to WRITE. The module supports a TARGET DEVICE
parameter value of 500CPU or PLC5. In order to complete the configuration of
the MSG instruction, select the SETUP SCREEN area of the MSG object. This
displays the following dialog box.