Reference DFNT ♦ ProLinx Gateway
Protocol Manual EtherNet/IP Explicit Messaging Client/Server
Page 84 of 124 ProSoft Technology, Inc.
July 24, 2013
5.2.16 Function Code #511 - Protected Typed Logical Write with Mask
(Three Address Fields)
0=Disabled, 1=Continuous and 2=Conditional.
This parameter defines the database address of the
data to be associated with the command. The first
word of data contains the bit mask and the second
word contains the data.
Minimum time in tenths of a second to wait before
polling with this command.
Number of data word values to be considered by the
function.
Swap type code for command: Always zero (0).
Address of unit to reach on the data highway.
Processor slot number in Control/CompactLogix rack.
Use -1 for PLC5 & SLC processors.
SLC file type letter as used in file name string. Valid
values for the system are N, S, F, A, ….
SLC file number to be associated with the command.
The parameter defines the element in the file where
write operation will start.
This parameter defines the sub-element for the
command. Refer to the AB documentation for a list of
valid sub-element codes.
This function writes one or more words of data from a PLC data table controlling
individual bits in the table. The bit mask used for the command is 0xFFFF. This
provides direct manipulation of the data in the device with the internal data of the
module. The function requires that all data associated with the command use the
same mask.