ILX69-PBS ♦ CompactLogix or MicroLogix Platform Contents
PROFIBUS Slave Communication Module User Manual
ProSoft Technology, Inc. Page 47 of 102
March 20, 2015
00.00.00.00 through
FF.FF.FF.FF
00.00.00.00 through
FF.FF.FF.FF
5.2.4 Configuration Parameters
Bus Address
The ILX69-PBS has two rotating address switches to set the network address from 0 to 99.
If you need to assign the ILX69-PBS to an address above 99, set both address switches to
0. The module will take the address parameter from the configuration data array.
Configuration
Address Parameter
Address switches are valid
Configuration parameter is valid
Invalid (will cause an initialization error)
Force User Configuration
If this value is set to 1, the ILX69-PBS will not start network communication until the master
and slave configurations match.
If this value is set to 0, the slave accepts the configuration sent from the master.