8.1 Technical Data - ILX69-PBS
Note: All technical data can be altered without notice.
ILX69-PBS
Parameter
Value
General
Description
PROFIBUS DP slave module
Function
PROFIBUS slave slot extension module for Rockwell
CompactLogix™ 1769 system which allows the PLC to
control exchange data on a PROFIBUS network.
Communication
Controller
Type
netX 100 processor
Integrated Memory
RAM
8 MB SDRAM
FLASH
16 MB serial Flash EPROM
Memory card
SD and SDHC card. Both types are supported if the card
features a SPI interface. The FAT12/16/32 formats are
supported. The exFAT format is not supported.
Capacity: Max. 4 GByte
Refer to section Removable Memory Card
SD Card Connector
e.g. FPS009-2405-0 push/push
Host Interface
1769 Backplane
Rockwell backplane interface:
Rockwell Mercury chip for 1769 backplane
PROFIBUS
Communication
Supported communication
protocol
PROFIBUS DP slave
PROFIBUS Interface
Transmission rate
9.6 kBit/s, 19.2 kBit/s, 31.25 kBit/s, 45.45 kBit/s,
93.75 kBit/s, 187.5 kBit/s, 500 kBit/s, 1.5 MBit/s,
3 MBit/s, 6 MBit/s, 12 MBit/s
Interface Type
RS-485, according EN 50170, refer to section PROFIBUS
Interface
Galvanic Isolation
Isolated
Isolation Voltage
500 VDC (from backplane)