Prosoft-technology ILX69-PBS Manual de usuario Pagina 92

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 102
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 91
Contents ILX69-PBS CompactLogix or MicroLogix Platform
User Manual PROFIBUS Slave Communication Module
Page 92 of 102 ProSoft Technology, Inc.
March 20, 2015
8.2 Technical Data - PROFIBUS
Parameter
Description
Maximum number of cyclic input data
244 bytes
Maximum number of cyclic output data
244 bytes
Maximum number of acyclic data (read/write)
240 bytes/telegram
Maximum number of modules
24
Configuration data
Max. 244 bytes
Parameter data
237 bytes application specific parameters
Acyclic communication
DP V1 Class 1 Read/Write
DP V1 Class 1 Alarm
DP V1 Class 2 Read/Write/Data Transport
Baud rate
9.6 kBits/s, 19.2 kBits/s, 31.25 kBits/s, 45.45 kBits/s, 93.75 kBits/s,
187.5 kBits/s, 500 kBits/s, 1.5 MBits/s, 3 MBits/s, 6 MBits/s, 12
MBit/s
Auto baudrate detection is supported
Data transport layer
PROFIBUS FDL
Limitations
SSCY1S Slave to slave communication state machine not
implemented.
Data exchange broadcast not implemented.
Configuration by database not implemented yet.
I&M LR services other than Call-REQ/RES are not supported yet.
Reference to firmware/stack version
V2.7.x.x