ILX69-PBS ♦ CompactLogix or MicroLogix Platform Contents
PROFIBUS Slave Communication Module User Manual
ProSoft Technology, Inc. Page 55 of 102
March 20, 2015
Slave Status
A 128 byte Slave Status field is transferred to the user program via the input data area
image. It contains the ILX69-PBS status, beginning with byte 8 of the input region. The
status information encompasses 32 bytes of static information and 96 bytes bytes reserved
for the extended status field. The content of the extended status is controlled by the
command "ExtStaSelect" byte in the Device Command Register in the user program (byte
offset 8 to 9).
Shows the extended status
information that is currently
transmitted in the field
"Extended Status Information"
0 = No extended status information
1 = Firmware version
2 = Slave configuration
3 = Master configuration
4 = Parameter data
6 = Reserved
Number of valid bytes in the
region "Extended Status
Information"
Depends on the selected extended status
0 = 0 Byte
1 = 32 Byte
2 = 49 Byte
3 = 49 Byte
4 = 33 Byte
6 = 80 Byte
Baud Rate on PROFIBUS
network
12000 = 12 MBaud
6000 = 6 MBaud
3000 = 3 MBaud
1500 = 1.5 MBaud
500 = 500 kBaud
187 = 187.5 kBaud
93 = 93.75 kBaud
9 = 9.6 kBaud
0 = Not detected
D0 = Parameter data changed
D1 = Configuration data changed
D2 to D7 = Not Applicable
Slave identification number
Indication of bus activity
Extended Status Information