Contents MVI56E-DNPNET ♦ ControlLogix Platform
User Manual DNPNET Ethernet Client/Server Communication Module
Page 116 of 140 ProSoft Technology, Inc.
February 13, 2015
Configure the Client database
sizes
DNPNET_List_Entry_Counts_type
Lengths of the seven Overide
lists
DNPNET_BinIn_Class_Override_type[1
0]
Assigning classes to individual
points
DNP_Server_Analog16_I
nputs
DNPNET_A16in_ClassDeadband_Over
ride_type[10]
Assigning class/deadbands to
individual points
DNP_Server_Analog32_I
nputs
DNPNET_A32in_ClassDeadband_Over
ride_type[10]
Assigning class/deadbands to
individual points
DNPNET_FLTin_ClassDeadband_Over
ride_type[10]
Assigning class/deadbands to
individual points
DNPNET_DBLin_ClassDeadband_Over
ride_type[10]
Assigning class/deadbands to
individual points
DNPNET_Server_List_type[5]
List of servers the Client
connects to
DNPNET_Client_Commands[5]
List of commands the Client
sends to servers
4.4.2 DNPNET.DATA. controller tags
DNPNET.DATA.DNP_Outp
uts.Binary
0 to 8000 points (500
16-bit words)
Object 12 binary INTs from
module’s server database
DNPNET.DATA.DNP_Outp
uts.Analog16
0 to 5000 points (if all
other DNP_Outputs are
0)
Object 41 analog INTs from
module’s server database
DNPNET.DATA.DNP_Outp
uts.Analog32
0 to 2500 points (if all
other DNP_Outputs are
0)
Object 41 analog DINTs from
module’s server database
DNPNET.DATA.DNP_Outp
uts.Float
0 to 2500 points (if all
other DNP_Outputs are
0)
Object 41 analog REALs
from module’s server
database
DNPNET.DATA.DNP_Outp
uts.Double
0 to 1250 points (if all
other DNP_Outputs are
0)
Object 41 analog double
precision floats from
module’s server database
DNPNET.DATA.DNP_Input
s
.Binary
0 to 8000 points (‘500’
16-bit words)
Object 1 binary INTs for
module’s server database
DNPNET.DATA.DNP_Input
s.Analog16
0 to 5000 points (if all
other DNP_Inputs are
0)
Object 30 analog INTs for
module’s server database
DNPNET.DATA.DNP_Input
s.Analog32
0 to 2500 points (if all
other DNP_Inputs are
0)
Object 30 analog DINTs for
module’s server database
Comentarios a estos manuales