MVI56E-DNPNET ♦ ControlLogix Platform Contents
DNPNET Ethernet Client/Server Communication Module User Manual
ProSoft Technology, Inc. Page 41 of 140
February 13, 2015
2 Edit the length inside the [ ] of the DNPNET_Server_List[ ] Data Type.
3 When finished, click APPLY and then click YES to accept changes to the Data Type
4 Click OK to close this window.
5 Save and download the RSLogix 5000 program to the processor.
6 Reboot the MVI56E-DNPNET for changes to be downloaded to the module.
2.3.8 DNPNET.CONFIG.DNP_Client_Commands[x]
Configures a list of commands the MVI56E-DNPNET client sends to DNP3 Ethernet servers.
The default array size is five, and the maximum is 300.
DNPNET.CONFIG.DNP_Client
_Commands[x].Port_Flags
Bits in the Port/Flags parameter are dependent
on the data type. Clear 3rd bit to disable. Set
5th bit to select IED DB for write functions.
DNPNET.CONFIG.DNP_Client
_Commands[x].Server_Addres
s
This parameter specifies the DNP server
address on the DNP network to which the
command will be sent. (This is not the IP
address of the server). The parameter has a
range of 0 to 65535. The value of 65535 is
reserved for broadcast messages. Verify that
the server configuration information is set up in
the module for each server defined in the
command list.