MVI56E-DNPNET ControlLogix Platform Contents
DNPNET Ethernet Client/Server Communication Module User Manual
ProSoft Technology, Inc. Page 23 of 140
February 13, 2015
8 Select the MVI56(E)DNPNET_ADDON_RUNG_V1_0.L5X file, and then click IMPORT.
9 This action opens the IMPORT CONFIGURATION window. Click TAGS under MAINROUTINE
to show the tags that will be imported.
10 Associate the I/O connection variables to the correct module in the corresponding slot
number. The default values are Local:1:I and Local:1:O and must be edited if the card is
placed in a slot location other than slot 1 (Local:1:x means the card is located in slot 1).
Since the second card is placed in slot 2, edit the FINAL NAME to Local:2:I and Local:2:O.