MVI69-HART ♦ CompactLogix Platform Reference
HART Multi-drop Master Communication Module User Manual
ProSoft Technology, Inc. Page 111 of 169
March 29, 2012
Offset Content Description
33 Current Command This field contains the index of the current command
to execute.
34 Command Request Count This field contains the total number of request
messages issued on the port.
35 Command Response Count This field contains the total number of response
messages received from devices on the network.
36 Configuration Error Word Configuration error word (see table).
37 Current Error Code Current error code for port.
38 Last Error Code Last error code reported for port.
61 to 248 Reserved Not used.
249 Read Block ID Block identification code of 0 or -1 to indicate a status
data block.
The following table defines the contents of the configuration error word. Each bit
in the word corresponds to an error condition recognized when the module is
configured. There is a separate word for each application port. This data is
reported in the status data area previously defined.
Bit Code Description
0 0x0001 Enabled not set to Y or N
1 0x0002 Enable Handheld not set to Y or N
2 0x0004 Primary Master not set to Y or N
3 0x0008 Invalid Preambles (1 to 50)
4 0x0010 Invalid Short Address Retries (0 to 50)
5 0x0020 Invalid Long Address Retries (0 to 50)
6 0x0040 Invalid Retries After Error (0 to 50)
7 0x0080 Invalid Poll Time After Error (0 to 10000)
8 0x0100 Invalid DB Address Status
9 0x0200 Invalid Command Count
10 0x0400 Memory Error in allocating commands
11 0x0800 Memory Error in allocating command fixed data
12 0x1000 Memory Error in allocating TX/RX buffers
13 0x2000 HART Board not found
14 0x4000 Cannot initialize HART channel
15 0x8000
Each command in the command list for each HART channel has a word value for
a status/error code. This error data list can be read using the
Configuration/Debug Port and can be placed in the module’s internal database
using the Error/Status Offset parameter for each port. Accessing the Debug
capabilities of the module is accomplished by connecting a PC to the Debug port,
then running a terminal emulation program. This status/error code is the first
word of the Integer Data Block returned from every HART command executed.
This word has information about the execution of the command by the HART
device.