Module Configuration MVI69-HART ♦ CompactLogix Platform
User Manual HART Multi-drop Master Communication Module
Page 34 of 169 ProSoft Technology, Inc.
March 29, 2012
Commands Supported by the Module
The format of each command in the list is independent on the function being
executed. All parameters in the command table must be entered. Only one
parameter is optional, the Fixed Data field, which contains data to be sent to a
HART device. The tables below list the functions supported by the module:
HART Universal Commands Set
Command Definition
00 Read Unique Identifier
01 Read Primary Variable
02 Read Current And Percent Of Range
03 Read Dynamic Variables
06 Write Polling Address
07 Read Loop Configuration
08 Read Dynamic Variable Classifications
09 Read Device Variables with Status
11 Read Unique Identifier Associated With Tag
12 Read Message
13 Read Tag Descriptor Date
14 Read PV Sensor Info
15 Read Output Information
16 Read Final Assembly Number
17 Write Message
18 Write Tag Descriptor Date
19 Write Final Assembly Number
20 Read Long Tag
21 Read Unique Identifier Associated With Long Tag
22 Write Long Tag
HART Common Practice Commands Set
Command Definition
33 Read Transmitter Variables
34 Write Damping Value
35 Write Range Values
36 Set Upper Range Value
37 Set Lower Range Value
38 Reset Configuration Changed Flag
39 EEPROM Control
40 Enter Exit Fixed Current Mode
41 Perform Transmitter Self Test
42 Perform Master Reset
43 Set PV Zero