MVI69-HART ♦ CompactLogix Platform Module Configuration
HART Multi-drop Master Communication Module User Manual
ProSoft Technology, Inc. Page 45 of 169
March 29, 2012
The user can configure the command parameters as described in the following
table.
Index Parameter Value Observation
1 Enable 1 The command is sent continuously
2 Float DB
Address
300 The damping value response will be copied to the
internal database starting at word-address 300
(occupies addresses 300 to 301)
3 Poll Interval 0 The command is sent without any delay
4 Word Count 2 The command returns 10 words of floating point
data
5 Swap Code 3 The bytes in each returned floating point word are
swapped
6 Short Address 0 This command is sent to the Hart slave device using
short address 0
7 Function Code 34 The command function 4 (WRITE DAMPING
VALUE) is used in this example
8 Int. DB Address
320 The integer data will copied to the database word-
address 320
9 Word Count 1 The command returns 1 word of integer data
10 Swap Code 3 The bytes in each returned integer data will be
swapped
11 Use Long 1 This command executes using Long Address
12 Enable
Address
-1 This command does not use this feature
13 DB Done
Address
-1 This command does not use this feature
14 DB Write
Address
800 The floating point value located at byte-address 800
(word-address 400) will be used as the damping
value to be written to the HART device
15 DB Swap Code
3 The bytes in each returned integer data will be
swapped
16 Byte Count 4 The command will write 4 bytes (2 words) to the
HART device, since the damping value uses floating
point format (2 words)
17 Fixed Data This command does not use this feature
The user would have to verify that addresses 300 and 320 are located inside the
Read Data area (read from the MVI database to the PLC processor). Address
400 would have to be located inside the Write Data area (written from the PLC
processor to the MVI database).