5.1.2 Hardware Specifications
Specification Description
Dimensions Standard 1769 Single-slot module
Current Load 800 mA max @ 5 VDC
Power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus)
Operating Temp. 32° F to 140° F (0° C to 60°C)
Storage Temp. -40° F to 185° F (-40° C to 85° C)
Relative Humidity 5% to 95% (with no condensation)
LED Indicators Battery and Module Status
Application Status
Serial Port Activity
CFG Port Activity
CFG Port (CFG) RJ45 (DB-9F with supplied cable)
RS-232 only
No hardware handshaking
App Ports (P1,P2)
(Serial modules)
RS-232, RS-485 or RS-422 (jumper selectable)
RJ45 (DB-9F with supplied cable)
RS-232 handshaking configurable
500V Optical isolation from backplane
Shipped with Unit RJ45 to DB-9M cables for each port
6-foot RS-232 configuration Cable