Prosoft-technology MVI69-MCM Manual de usuario Pagina 58

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 167
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 57
Configuring the MVI69-MCM Module MVI69-MCM ♦ CompactLogix or MicroLogix Platform
User Manual Modbus Communication Module
Page 58 of 167 ProSoft Technology, Inc.
March 22, 2011
Response Timeout
0
TO
65535 milliseconds
This parameter sets the command response timeout period in 1 millisecond
increments. This is the time that a port configured as a Master will wait for a
response from the addressed slave before re-transmitting the command (Retries)
or skipping to the next command in the Command List. The value to set depends
on the communication network used and the expected response time (plus a little
extra) of the slowest device on the network.
Retry Count
0 to 10
This parameter specifies the number of times a command will be retried if it fails.
Error Delay Counter
0 to
65535
This parameter specifies the number of polls to skip on the slave before trying to
re-establish communications. After the slave fails to respond, the Master will skip
commands to be sent to the slave the number of times entered in this parameter.
Vista de pagina 57
1 2 ... 53 54 55 56 57 58 59 60 61 62 63 ... 166 167

Comentarios a estos manuales

Sin comentarios