Block Transfer Size = 120
Comm Format Data - INT
Slot The slot number in the rack where the module is installed
Input Assembly Instance 101
Input Size 122
Output Assembly Instance 100
Output Size 121
Configuration Assembly Instance 102
Configuration Size 0
Block Transfer Size = 240
Field Recommended Value
Type 1769-MODULE Generic 1769 Module
Parent Local
Name MVI69
Description MVI69 Application Module
Comm Format Data - INT
Slot The slot number in the rack where the module is installed
Input Assembly Instance 101
Input Size 242
Output Assembly Instance 100
Output Size 241
Configuration Assembly Instance 102
Configuration Size 0
5 Click N
EXT
to continue.
6 Select the
R
EQUEST
P
ACKET
I
NTERVAL
value for scanning the I/O on the
module. This value represents the minimum frequency the module will handle
scheduled events. This value should not be set to less than 1 millisecond.