Reference MVI69-MCM ♦ CompactLogix or MicroLogix Platform
User Manual Modbus Communication Module
Page 104 of 167 ProSoft Technology, Inc.
March 22, 2011
5.1.3 General Specifications - Modbus Master/Slave
Communication
parameters
Baud Rate: 110 to 115K baud
Stop Bits: 1 or 2
Data Size: 7 or 8 bits
Parity: None, Even, Odd
RTS Timing delays: 0 to 65535 milliseconds
Modbus Modes RTU mode (binary) with CRC-16
ASCII mode with LRC error checking
Floating Point
Data
Floating point data movement supported, including configurable
support for Enron, Daniel
®
, and other implementations
Modbus Function
Codes Supported
1: Read Coil Status
2: Read Input Status
3: Read Holding Registers
4: Read Input Registers
5: Force (Write) Single Coil
6: Preset (Write) Single
Holding Register
8: Diagnostics (Slave Only,
Responds to
Subfunction 00)
15: Force( Write) Multiple Coils
16: Preset (Write) Multiple
Holding Registers
17: Report Slave ID (Slave Only)
22: Mask Write Holding
Register (Slave Only)
23: Read/Write Holding
Registers (Slave Only)