Diagnostics and Troubleshooting MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual PROFIBUS DPV1 Master
Page 182 of 255 ProSoft Technology, Inc.
March 22, 2011
The following tables will help you to troubleshoot different scenarios and the LED
behavior.
4.2.4 Legacy Mode (Use Legacy Mode = Yes)
Scenario Debug Access After Power Up LED Behavior After Power Up
- Module located in slot that is not
configured
OR
- No processor
OR
- Neither sample logics loaded to
processor (LEGACY or FLEX)
No
(Waiting for connection to
processor)
MSTR STAT= OFF
COM STAT=OFF
DBASE STAT=GREEN
TKN HLD= OFF
OK = RED
BP ACT = AMBER
APP STATUS= AMBER
LEGACY Ladder loaded to
processor (module is inserted in
configured slot)
Yes MSTR STAT= GREEN
COM STAT= GREEN or OFF (depends if the
module is communicating with PROFIBUS
slaves)
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = AMBER
APP STATUS= AMBER
FLEX Ladder Yes MSTR STAT= GREEN (1sec) /RED (2 secs)
COM STAT= OFF
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = OFF
APP STATUS= AMBER