MVI56-PDPMV1 ♦ ControlLogix Platform Diagnostics and Troubleshooting
PROFIBUS DPV1 Master User Manual
ProSoft Technology, Inc. Page 183 of 255
March 22, 2011
4.2.5 Flex Mode (Use Legacy Mode=No)
Scenario Debug Access After Power Up LED Behavior After Power Up
- Module located in slot that is not
configured
OR
- No processor
OR
- Neither sample logics loaded to
processor (LEGACY or FLEX)
No
(Waiting for connection to
processor)
MSTR STAT= OFF
COM STAT=OFF
DBASE STAT=GREEN
TKN HLD= OFF
OK = RED
BP ACT = AMBER
APP STATUS= AMBER
LEGACY Ladder Yes MSTR STAT= RED
COM STAT= OFF
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = OFF
APP STATUS= AMBER
FLEX Ladder Yes MSTR STAT= GREEN
COM STAT= GREEN or OFF (depends if
the module is communicating with
PROFIBUS slaves)
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = AMBER
APP STATUS= OFF