Configuring the MVI56-PDPMV1 Module MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual PROFIBUS DPV1 Master
Page 90 of 255 ProSoft Technology, Inc.
March 22, 2011
For this example, we will configure thirty-two (32) words of output and eight
(8) words of input. These input and output words are assigned to addresses
within the MVI56-PDPMV1 module's internal database.
For each new slave added to the PROFIBUS network, PCB automatically
converts the input/output byte addresses to word input/output addresses for
the tag database in the processor.
Tip: To make it easier to view the data from individual slaves, give each slave a meaningful name,
and place each slave's I/O areas in contiguous blocks. Use the Processor Network Memory Map
(page 104) as an aid to cross-referencing the slave I/O data in RSLogix 5000.