Prosoft-technology MVI56-PDPMV1 Manual de usuario Pagina 242

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 255
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 241
Reference MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual PROFIBUS DPV1 Master
Page 242 of 255 ProSoft Technology, Inc.
March 22, 2011
Byte Offset
Start End Name Description
110 111 Reserved Reserved for future use
112 113 Module backplane read count Rollover counter of the number of MVI56-PDPMV1 to processor
backplane read data transfers
114 115 Module backplane write count Rollover counter of the number of MVI56-PDPMV1 to processor
backplane write data transfers
116 117 Module backplane error count Rollover counter of the number of MVI56-PDPMV1 to processor
backplane data transfers that have failed
118 119 File Error Word Bitmapped value that indicates which files are not present
Bit 0: Problem with PDPMV1.CFG file
Bit 1: Not used
Bit 2: Problem with PDPMV1.DDB file
Bit 3: Problem with PDPMV1.XML file
Bits 4 to 15 not used.
If this word has a value other than 0, the CFG ERR LED on the
module will be illuminated.
120 145 Reserved Reserved for future use
146 147 In mailbox queue count Number of message in the in mailbox queue
148 149 Out mailbox queue count Number of message in the out mailbox queue
150 151 Alarm queue count Number of message in the alarm queue
152 153 Last out mailbox message ID
processed from output image
Last out mailbox message ID processed from output image
154 155 Current in mailbox control index Current in mailbox control index
156 157 Current alarm control index Current alarm control index
158 496
Reserved for future use
496 497
Index of Output image to receive (1 to 4 for data, 0 or -1 if no
data)
498 499
Block index of -1 or 0 for status block
Output Data Block (Block ID = 1 to n)
This block contains the PROFIBUS output data to be sent from the processor to
the module.
Output Data Block Format (Output Image)
You can find the contents of the Output Data Block (Output Image) in the
MVI56PDPMV1.Output user controller tags in RSLogix.
Byte Offset
Start End Name Description
0 0 Write Block ID Block number of this write block 1 to n
1 2 PROFIBUS CRC32 value Computed for PROFIBUS Config
Vista de pagina 241
1 2 ... 237 238 239 240 241 242 243 244 245 246 247 ... 254 255

Comentarios a estos manuales

Sin comentarios