MVI69-PDPMV1 CompactLogix or MicroLogix Platform Mailbox Messaging
PROFIBUS DPV1 Master User Manual
ProSoft Technology, Inc. Page 113 of 225
July 8, 2011
Features Supported 1
Identifies the supported Class 2-service functionality as follows:
bit 0: DPV1_RW. Set if C2_Read & C2_Write services
are supported.
bits 1 through 7: (reserved for future use)
Default value is 01h.
Features Supported 2
(Reserved for future use.)
Profile Supported 1 & 2
Identifies the supported service functionality regarding the used profile definition.
The meaning of these registers are profile- and vendor specific. By default, both
are set to 00h.
Profile Ident Number
This parameter identifies a unique profile definition. The Profile Ident Number is
taken from the pool of Ident Numbers managed by the Profibus User
Organisation (PNO).
Range: 0...65535.
0 = No profile (default).
S_Type
This parameter indicates the presence of the optional Network/MAC address of
the source.
bit 0: 1 = A Network/MAC address is present in
S_Address.
0 = The source is the endpoint of the connection.
bits 1 through 7: (reserved for future use)
Default value is 00h.
S_Length
This parameter specifies the length of the S_Address parameter (see table
below).
Default value is 02h.