MVI69-PDPMV1 CompactLogix or MicroLogix Platform Diagnostics and Troubleshooting
PROFIBUS DPV1 Master User Manual
ProSoft Technology, Inc. Page 137 of 225
July 8, 2011
5.1.3 Viewing the Fieldbus Data from the MVI69-PDPMV1’s
Configuration/Debug Menu
Note: For this procedure, you must connect a serial cable from the serial port on your PC to the
RJ45 to DB9M adaptor cable on the MVI69-PDPMV1 module. If your 1769 processor is equipped
with a built-in Ethernet port, such as the L32E or L35E processors, you may make a diagnostic
connection to the module using CIPconnect.
1 In ProSoft Configuration Builder, select the MVI69-PDPMV1 module, then
click the right mouse button to open a shortcut menu.
2 On the shortcut menu, choose D
IAGNOSTICS. This action opens the
Diagnostics dialog box.
3 Press [?] to display the Main menu, and then press [2] to view Fieldbus data.
4 Note the value in Operation State. If the Master and the slave are
communicating correctly, the operation state will be C0 (hex).